Analog /digital module for 2 digital inputs/outputs and 1 analog
input/output
Analog input
Description of the input |
Current input |
Current input signal |
4 mA ... 20 mA |
Input resistance current
input |
< 170 Ω |
Analog output
Output name |
Current output |
Load/output load current
output |
700 Ω (at UB = 24
V, RB = [UB-10 V] / 20 mA) |
Digital input
Input voltage range |
5 V AC/DC ... 30 V AC/DC |
Switching threshold "0"
signal, voltage |
Max. 1.5 V DC |
Switching threshold "1"
signal voltage |
Min. 5 V DC |
Digital output
Output name |
Relay output |
Number of outputs |
2 |
Maximum switching voltage |
30 V AC/DC (EC Declaration of Conformity) |
|
30 V DC (With UL approval) |
|
250 V AC (With UL approval) |
Limiting continuous current |
0.5 A (EC Declaration of Conformity) |
General data
Ambient temperature (operation) |
-20 °C ... 65 °C |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Degree of protection |
IP20 |
Mounting position |
Any |
Assembly instructions |
on TS 35 profile rail acc. to EN
60715 |
Housing material |
Polyamide PA non-reinforced |
Length |
99 mm |
Width |
22.5 mm |
Height |
114.5 mm |
Conformity |
CE compliant |
ATEX approval |
II 3 G Ex nAC IIC T5 X |
IECEX approval |
Ex nL IIC T5 |
UL, USA / Canada |
Class I, Div. 2, Groups A, B, C,
D |
Connection data
Conductor cross section
solid min. |
0.2 mm2 |
Conductor cross section
solid max. |
4 mm2 |
Conductor cross section
stranded min. |
0.2 mm2 |
Conductor cross section
stranded max. |
2.5 mm2 |
Conductor cross section
AWG/kcmil min. |
24 |
Conductor cross section
AWG/kcmil max |
14 |
Type of connection |
Screw connection |
Stripping length |
8 mm |
Screw thread |
M3 |
|
Block diagram
|
Part#: RAD-IN+OUT-2D-1A-I
Manufacturer#: 2867322
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|