Product description
With the MINI-SYS-PS power supply, additional modules can be supplied with 24 DC using the optional DIN rail connectors. The low design depth of 95 mm is a particular advantage for use in surroundings with a low height. The system power supply particularly simplifies the power supply of the FO transmission system PSI-MOS as well as of the analog 6 mm MCR measuring transducer. In this way it emphasizes the seamless character of the INTERFACE product range.
Even without the DIN rail connector, the flat power supply unit 24 V/1.5 A is suitable for many applications in areas in which space is restricted, as the housing is 12 mm flatter than other comparable solutions.
The electronic short circuit and idling-proof device is connected to single-phase AC networks with nominal voltages of 100 V AC to 240 V AC or to two of the phase conductors of three-phase networks with a linked voltage of this value. In the event of a malfunction, the output voltage is limited to 30 V DC.
Due to the U/I characteristic curve with POWER BOOST, miniature circuit breakers blow reliably. For function monitoring, there is the floating DC OK output and the DC OK LED. High operational reliability is provided by the mains failure bridging time of more than 20 ms under full load.
Ambient temperatures can be in the range of -25°C to +70°C, whereby the power reserve of approx. 25% up to 40°C is permanently available.
100 V AC ... 240 V AC |
Input data
Nominal input voltage |
100 V AC ... 240 V AC |
AC input voltage range |
85 V AC ... 264 V AC |
AC frequency range |
45 Hz ... 65 Hz |
Current consumption |
Approx. 0.75 A (120 V AC) |
|
0.45 A (230 V AC) |
Inrush surge current |
< 15 A (0.6 A2s) |
Power failure bypass |
> 35 ms (120 V AC) |
|
> 150 ms (230 V AC) |
Input fuse |
3.15 A (slow-blow, internal) |
Recommended backup fuse |
6 A |
|
10 A |
|
16 A (characteristic B) |
Name of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Output data
Nominal output voltage |
24 V DC ±1% |
Setting range of the output voltage |
22.5 V DC ... 28.5 V DC |
Output current |
1.5 A (up to 60°C) |
|
2 A (with POWER BOOST) |
Connection in parallel |
Yes, for redundancy and increased capacity.Maximum of 2 devices for redundancy on DIN rail connector. |
Connection in series |
No |
Max. capacitive load |
Unlimited |
Control deviation |
< 1 % (change in load, static 10% ... 90%) |
|
< 3 % (change in load, dynamic 10% ... 90%) |
|
< 0.1 % (change in input voltage ±10%) |
Residual ripple |
< 40 mVPP (20 MHz) |
Peak switching voltages idling |
(20 MHz) |
Peak switching voltages nominal load |
< 20 mVPP (20 MHz) |
Maximum power dissipation idling |
2.5 W |
Power loss nominal load max. |
12 W |
General data
Width |
35 mm |
Height |
99 mm |
Depth |
95 mm |
Weight |
0.25 kg |
Operating voltage display |
LED green |
Efficiency |
> 84 % |
Insulation voltage input/output |
3 kV (routine test) |
|
4 kV (type test) |
Degree of protection |
IP20 |
Class of protection |
II (in an enclosed control cabinet) |
MTBF |
> 500 000 h in acc. with IEC 61709 (SN 29500) |
Ambient temperature (operation) |
-25 °C ... 70 °C (> 60°C derating) |
Ambient temperature (storage/transport) |
-40 °C ... 85 °C |
Max. permissible relative humidity (operation) |
95 % (at 25°C, no condensation) |
Mounting position |
Horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
Can be aligned: Horizontal 0 cm, vertical 5 cm |
Electromagnetic compatibility |
Conformance with EMC directive 89/336/EEC |
Emitted interference |
EN 50081-2 |
Immunity to interference |
EN 61000-6-2 |
Standard – Electrical equipment of machines |
EN 60204 |
Standard – Safety transformers for switched-mode power supply units |
EN 61558-2-17 |
Standard - Electrical safety |
EN 60950/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage |
EN 60950 (SELV) and EN 60204 (PELV) |
Standard - Safe isolation |
DIN VDE 0100-410 |
|
DIN VDE 0106-1010 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment |
DIN VDE 0106-101 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
UL approvals |
UL/C-UL listed UL 508 |
|
UL/C-UL Recognized UL 60950 |
|
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D |
Connection data, input
Type of connection |
COMBICON screw/plug connection |
Conductor cross section solid min. |
0.2 mm2 |
Conductor cross section solid max. |
2.5 mm2 |
Conductor cross section stranded min. |
0.2 mm2 |
Conductor cross section stranded max. |
2.5 mm2 |
Conductor cross section AWG/kcmil min. |
24 |
Conductor cross section AWG/kcmil max |
12 |
Stripping length |
7 mm |
Screw thread |
M 3 |
Connection data, output
Type of connection |
COMBICON screw/plug connection |
Conductor cross section solid min. |
0.2 mm2 |
Conductor cross section solid max. |
2.5 mm2 |
Conductor cross section stranded min. |
0.2 mm2 |
Conductor cross section stranded max. |
2.5 mm2 |
Conductor cross section AWG/kcmil min. |
24 |
Conductor cross section AWG/kcmil max |
12 |
Stripping length |
7 mm |
Signaling
Output name |
DC OK floating |
Output description |
UOUT > 21.5 V: Contact closed |
Maximum switching voltage |
≤ 30 V AC/DC |
Output voltage |
30 V AC/DC |
Continuous load current |
≤ 1 A |
Status display |
"DC OK" LED green |
Note on status display |
UOUT > 21.5 V: LED lights up |
Conductor cross section solid min. |
0.2 mm2 |
Conductor cross section solid max. |
2.5 mm2 |
Conductor cross section stranded min. |
0.2 mm2 |
Conductor cross section stranded max. |
2.5 mm2 |
Conductor cross section AWG/kcmil min. |
24 |
Conductor cross section AWG/kcmil max |
12 |
Tightening torque, min |
0.5 Nm |
Tightening torque max |
0.6 Nm |
Screw thread |
M 3 |
|
Block diagram
Diagram
|
Part#: MINI-SYS-PS-100-240AC/24DC/1.5
Manufacturer#: 2866983
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|